HoneywellHoneywell C6097A, B Series Pressure Switch

Honeywell C6097A, B Series Pressure Switch

C6097 series pressure switches are designed to detect the upper or lower limit pressures of either gas or air supply in combustion systems.

View Photos
Honeywell C6097A, B Series Pressure Switch Honeywell C6097A, B Series Pressure Switch Honeywell C6097A, B Series Pressure Switch

For use with natural gas, liquid propane (LP) gas, or air

Diaphragm-actuated safety-limit switch

Switch can be wired to turn on alarm

C6097A models break control circuit at setpoint on pressure fall

C6097B models break control circuit at setpoint on pressure rise

Lockout with manual reset and recycle options

Lockout models have external manual reset button

Removable transparent cover protects scaleplate and adjusting knob

1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train

Optional switch position indicator lamp available

IP54 enclosure standard

32003041-001 C6097 Cover for manual reset models.
32003040-001 C6097 Cover for recycle models.
32003039-001 Position Indication Lamp Kit.

Models:

C6097A Pressure Switch:

Breaks a circuit when pressure falls to scale setting.

C6097B Pressure Switch:

Breaks a circuit when pressure rises to scale setting.

Ambient Temperature:

-40 ~ 60°C

Scale:

0.10 to 1.25 kPa

0.75 to 5.23 kPa

3.0 to 15 kPa

10.3 to 48 kPa

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes