HoneywellHoneywell R4343 Flame Relay

Honeywell R4343 Flame Relay

The R4343D/E series is a flame switch for an intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.

Flame current meter jack socket on the front of the unit permits monitoring of flame signal strength by using any appropriate microampere meter (0-10uA minimum scale)
Plugs in and mounts into a sub-base (comes standard) for surface mounting.

Providing an indication of absence or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.

The R4343D models will operate also with the "Satronic" IRD1020 range of infrared sensors. Note that this combination is NOT CE approved for use on installations that fall under the GAD (Gas Appliances Directive).

View Photos
Honeywell R4343 Flame Relay

Protection Class:

IP40

Ambient Temperature:

-15 to 60°C

Maximum Humidity:

90% RH

Outputs:

1xDPDT

Operation:

Intermittent

Additional Notes:

R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors

R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C704

Model:

Description:

117053/U  

Cable (ca. 250mm) with jack plug for remote 0..15 micro-ampere flame signal reading. For use with jack plug socket on the front of DBC2000 and R4343 or on plug-in amplifier of R4348.

C7008 Series

Industrial flame rod.

C7027 Series

MiniPeeper standard UV detector and IP54 protection.

C7035 Series

MiniPeeper with field replaceable tube and IP65 protection.

C7044 Series

MiniPeeper UV sensor with side view and IP54 protection.

Model

Supply Voltage

Flame Detector

FFRT

R4343E1006

110 ~ 120 VAC

UV

<1s

R4343E1014

220 ~ 240 VAC

UV

<1s

R4343E1048

115/230 VAC

UV

<2s

For use in commercial and industrial burners

Enquire Now
 Subscribe to newsletter